Capacity Curtailment on the SI-IT border for delivery day 30/04/2020
1. TSO(s) :
TERNA
2. Identification of affected Long Term Transmission Rights
Slovenia to Italy
3. Triggering event :
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period :
Slovenia to Italy
30/04/2020
§ 09:00 – 10:00 190 MW
§ 17:00 – 18:00 190 MW
§ 23:00 – 24:00 190 MW
5. Amount of LTTR remaining after curtailment :
Slovenia to Italy
30/04/2020
§ 09:00 – 10:00 164 MW
§ 17:00 – 18:00 134 MW
§ 23:00 – 24:00 123 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment :
Voltage stability issue on the Italian Electrical system.
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) ?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.