Capacity Curtailment on the DE-NL border for delivery day 12/01/2020

Published:

1. TSO(s): TenneT TSO B.V.

2. Identification of affected Long Term Transmission Rights

Germany -> Netherlands

3. Triggering event :

☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation

4. Affected volume in MW / hour for each concerned period :

12/01/2020

07:00 – 08:00 1081 MW

08:00 – 09:00 1081 MW

09:00 – 10:00 1081 MW

10:00 – 11:00 1081 MW

11:00 – 12:00 1081 MW

12:00 – 13:00 1081 MW

13:00 – 14:00 1081 MW

14:00 – 15:00 1081 MW

15:00 – 16:00 1081 MW

16:00 – 17:00 1081 MW

5. Amount of LTTR remaining after curtailment :

12/01/2020

07:00 – 08:00 435 MW

08:00 – 09:00 435 MW

09:00 – 10:00 1056 MW

10:00 – 11:00 1056 MW

11:00 – 12:00 1057 MW

12:00 – 13:00 1057 MW

13:00 – 14:00 1060 MW

14:00 – 15:00 431 MW

15:00 – 16:00 431 MW

16:00 – 17:00 431 MW

6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:

Expected violation of operational security limits of physical transmission assets.

7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

The remedial actions considered in the FB DA CC process were assessed as not sufficient or ineffective to avoid the expected violation of operational security limit(s).