Capacity Curtailment on AT-IT borders for delivery day 14/03/2020
TSO(s) *: TERNA
Identification of affected Long Term Transmission Rights
Austria to Italy
Triggering event :
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
Affected volume in MW / hour for each concerned period :
Austria to Italy
14/03/2020
11:00 – 12:00 178 MW
12:00 – 13:00 178 MW
13:00 – 14:00 178 MW
14:00 – 15:00 178 MW
15:00 – 16:00 178 MW
16:00 – 17:00 178 MW
Amount of LTTR remaining after curtailment :
Austria to Italy
14/03/2020
11:00 – 12:00 150 MW
12:00 – 13:00 150 MW
13:00 – 14:00 150 MW
14:00 – 15:00 150 MW
15:00 – 16:00 150 MW
16:00 – 17:00 150 MW
Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Voltage stability issue on the Italian Electrical system
Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.