Capacity Curtailment on the FR-IT border for delivery day 11/10/2020
1. TSO(s) *: Terna; Swissgrid, Eles, RTE, APG
2. Identification of affected Long Term Transmission Rights
France to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
France to Italy
11/10/2020
01:00 – 02:00 2480 MW
02:00 – 03:00 2480 MW
03:00 – 04:00 2480 MW
04:00 – 05:00 2480 MW
05:00 – 06:00 2480 MW
06:00 – 07:00 2480 MW
07:00 – 08:00 2480 MW
08:00 – 09:00 2480 MW
11:00 – 12:00 2480 MW
12:00 – 13:00 2480 MW
13:00 – 14:00 2480 MW
14:00 – 15:00 2480 MW
15:00 – 16:00 2480 MW
16:00 – 17:00 2480 MW
17:00 – 18:00 2480 MW
5. Amount of LTTR remaining after curtailment:
France to Italy
11/10/2020
01:00 – 02:00 2418 MW
02:00 – 03:00 2099 MW
03:00 – 04:00 2032 MW
04:00 – 05:00 1851 MW
05:00 – 06:00 2032 MW
06:00 – 07:00 2032 MW
07:00 – 08:00 2418 MW
08:00 – 09:00 2418 MW
11:00 – 12:00 2381 MW
12:00 – 13:00 2099 MW
13:00 – 14:00 2099 MW
14:00 – 15:00 1920 MW
15:00 – 16:00 2032 MW
16:00 – 17:00 2360 MW
17:00 – 18:00 2360 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Reduction due to the following overloaded element(s): PST La Praz Saint Andre ; Lienz - Soverzene
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation