Capacity Curtailment on the FR-IT border for delivery day 21/10/2020
1. TSO(s) *: SWISSGRID
2. Identification of affected Long Term Transmission Rights
France to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
France to Italy
21/10/2020
21:00 – 22:00 2480 MW
22:00 – 23:00 2480 MW
23:00 – 24:00 2480 MW
5. Amount of LTTR remaining after curtailment:
France to Italy
21/10/2020
21:00 – 22:00 2412 MW
22:00 – 23:00 2412 MW
23:00 – 24:00 2223 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *?
Reduction due to the following overloaded element(s): 380kV Pradella - Y/Punt (N-2 DIVACA-REDIPUGLIA + DIVACA-PADRICIANO)
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation