Capacity Curtailment on the BG-GR border for delivery period 14-09-2025
1. TSO(s)*:
HTSO-TSO
2. Identification of affected Long Term Transmission Rights:
BG-GR
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
14-09-2025 09:00 - 10:00 800 MW
14-09-2025 10:00 - 11:00 800 MW
14-09-2025 11:00 - 12:00 800 MW
14-09-2025 12:00 - 13:00 800 MW
14-09-2025 13:00 - 14:00 800 MW
14-09-2025 14:00 - 15:00 800 MW
5. Amount of LTTR remaining after curtailment:
14-09-2025 09:00 - 10:00 482 MW
14-09-2025 10:00 - 11:00 389 MW
14-09-2025 11:00 - 12:00 389 MW
14-09-2025 12:00 - 13:00 389 MW
14-09-2025 13:00 - 14:00 389 MW
14-09-2025 14:00 - 15:00 482 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Voltage stability issue on the Greek Electrical system. In addition, it is expected extremely low demand which leads to lack of reserve, low system inertia conditions and as a result requires a minimum number of power plants on the grid.
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.