Capacity curtailment on FR-IT border for delivery day 15/03/2020

Published:

Dear Market Participants,

1. TSO(s) *:

TERNA

2. Identification of affected Long Term Transmission Rights

France to Italy

3. Triggering event :

☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation

4. Affected volume in MW / hour for each concerned period :

France to Italy

15/03/2020

§ 11:00 – 12:00 930 MW

§ 12:00 – 13:00 930 MW

§ 13:00 – 14:00 930 MW

§ 14:00 – 15:00 930 MW

§ 15:00 – 16:00 930 MW

§ 16:00 – 17:00 930 MW

5. Amount of LTTR remaining after curtailment :

France to Italy

15/03/2020

§ 11:00 – 12:00 746 MW

§ 12:00 – 13:00 168 MW

§ 13:00 – 14:00 292 MW

§ 14:00 – 15:00 292 MW

§ 15:00 – 16:00 839 MW

§ 16:00 – 17:00 839 MW

6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:

Voltage stability issue on the Italian Electrical system.

7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.