Capacity Curtailment on the FR-IT border for delivery day 10/08/2021
1.TSO(s) *:
Swissgrid
2. Identification of affected Long Term Transmission Rights
France to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
France to Italy
10/08/2021
21:00 - 22:00 1802 MW
22:00 - 23:00 1802 MW
23:00 - 24:00 1802 MW
5. Amount of LTTR remaining after curtailment:
France to Italy
10/08/2021
21:00 - 22:00 1742 MW
22:00 - 23:00 1742 MW
23:00 - 24:00 1621 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Reduction due to expected overloads on 380 kV Bulciago-Soazzo
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation