Capacity Curtailment on the FR-IT border for delivery day 20/07/2022
1.TSO(s) *:
Swissgrid
2. Identification of affected Long Term Transmission Rights
France to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
France to Italy
20/07/2022
09:00 – 10:00 2061 MW
10:00 – 11:00 2061 MW
11:00 – 12:00 2061 MW
12:00 – 13:00 2061 MW
13:00 – 14:00 2061 MW
14:00 – 15:00 2061 MW
15:00 – 16:00 2061 MW
16:00 – 17:00 2061 MW
17:00 – 18:00 2061 MW
18:00 – 19:00 2061 MW
19:00 – 20:00 2061 MW
20:00 – 21:00 2061 MW
21:00 – 22:00 2061 MW
22:00 – 23:00 2061 MW
23:00 – 24:00 2061 MW
5. Amount of LTTR remaining after curtailment:
France to Italy
20/07/2022
09:00 – 10:00 1852 MW
10:00 – 11:00 1852 MW
11:00 – 12:00 1852 MW
12:00 – 13:00 1744 MW
13:00 – 14:00 1744 MW
14:00 – 15:00 1744 MW
15:00 – 16:00 1639 MW
16:00 – 17:00 1639 MW
17:00 – 18:00 1639 MW
18:00 – 19:00 1897 MW
19:00 – 20:00 1897 MW
20:00 – 21:00 1897 MW
21:00 – 22:00 1999 MW
22:00 – 23:00 1999 MW
23:00 – 24:00 1788 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Expected overloading on 380kV Lavorgo – Musignano; Robbia-Gorlago + Robbia-S.Fiorano; 380kV Bulciago - Soazza
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.