Capacity Curtailment on the FR-IT border for delivery day 15/09/2020

Published:

1.            TSO(s) *: 

 

Swissgrid

 

2.       Identification of affected Long Term Transmission Rights

          France to Italy

3.       Triggering event:

 

☒Curtailment to ensure operation remains within Operational Security Limits

☐Curtailment due to Force Majeure

☐Curtailment due to emergency situation

 

4. Affected volume in MW / hour for each concerned period:

France to Italy

 

15/09/2020  

09:00 – 10:00  2051 MW
10:00 – 11:00  2051 MW
11:00 – 12:00  2051 MW
 

 

 

Amount of LTTR remaining after curtailment :
 

France to Italy

 

15/09/2020  

09:00 – 10:00  1900MW
10:00 – 11:00  1900 MW
11:00 – 12:00  1900 MW
            

         

6.       Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:  

 

-          Reduction due to the following overloaded element(s): 380kV Lavorgo-Musignano for period:

 

 

09:00 – 10:00  1900MW

10:00 – 11:00  1900 MW

11:00 – 12:00  1900 MW

 

 

7.       Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

 

During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.