Capacity Curtailment on the FR-IT border for delivery day 24/10/2020
TSO(s) *: Swissgrid
Identification of affected Long Term Transmission Rights
France to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
France to Italy
24/10/2020
03:00 – 04:00 2480 MW
04:00 – 05:00 2480 MW
05:00 – 06:00 2480 MW
06:00 – 07:00 2480 MW
21:00 – 22:00 2480 MW
22:00 – 23:00 2480 MW
23:00 – 24:00 2480 MW
5. Amount of LTTR remaining after curtailment:
France to Italy
24/10/2020
03:00 – 04:00 2386 MW
04:00 – 05:00 2386 MW
05:00 – 06:00 2386 MW
06:00 – 07:00 2386 MW
21:00 – 22:00 2138 MW
22:00 – 23:00 2138 MW
23:00 – 24:00 2427 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *? Reduction due to the following overloaded element(s): 380kV Sils - Soazza (N-2 ROBBIA-GORLAGO + ROBBIA-S.FIORANO);380kV Pradella - Y/Punt (N-2 BONADUZ-SILS).
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *? During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.