Capacity Curtailment on the FR-IT border for delivery day 18/11/2020

Published:

1.       TSO(s) *: TERNA, RTE, Swissgrid, APG, ELES

2.       Identification of affected Long Term Transmission Rights

          France to Italy

3.       Triggering event:

 

☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
 

4.       Affected volume in MW / hour for each concerned period:

         France to Italy

18/11/2020  

 

23:00 – 24:00  2448 MW 

 

5.       Amount of LTTR remaining after curtailment:

         France to Italy

18/11/2020  

 

23:00 – 24:00  2403 MW 

            

6.       Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:  

          Reduction due to the following overloaded element(s): 220kV Lienz - Soverzene (120,2%)  

 

          

7.       Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

         During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation