Capacity Curtailment on the SI-IT border for delivery day 25/10/2020

Published:

1. TSO(s) *: TERNA, APG, SWG, ELES, RTE

 

2. 2. Identification of affected Long Term Transmission Rights

Slovenia to Italy


3. Triggering event:

☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation

4. Affected volume in MW / hour for each concerned period:


Slovenia to Italy
25/10/2020

12:00 – 13:00 361 MW
13:00 – 14:00  361 MW
14:00 – 15:00  361 MW

5. Amount of LTTR remaining after curtailment:


Slovenia to Italy
25/10/2020

12:00 – 13:00 285 MW
13:00 – 14:00  285 MW
14:00 – 15:00  285 MW


6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *?

Violation Soverzene-Lienz

7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

 During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation