Capacity Curtailment on the SI-IT border for delivery day 01/11/2022
1.TSO(s) *:
Terna
2. Identification of affected Long Term Transmission Rights
Slovenia to Italy
3. Triggering event:
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
4. Affected volume in MW / hour for each concerned period:
Slovenia to Italy
01/11/2022
10:00 – 11:00 324MW
11:00 – 12:00 250MW
12:00 – 13:00 306MW
13:00 – 14:00 353MW
5. Amount of LTTR remaining after curtailment:
Slovenia to Italy
01/11/2022
10:00 – 11:00 420MW
11:00 – 12:00 420MW
12:00 – 13:00 420MW
13:00 – 14:00 420MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:
Voltage stability issue on the Italian Electrical system
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.