Capacity Curtailment on the SI-IT borders for delivery day 21/04/2020
1.
TSO(s) *: TERNA
Identification of affected Long Term Transmission Rights
Slovenia to Italy
Triggering event :
☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
TS
Affected volume in MW / hour for each concerned period :
Slovenia to Italy
21/04/2020
§00:00 – 01:00 362 MW
§01:00 – 02:00 362 MW
§02:00 – 03:00 362 MW
§03:00 – 04:00 362 MW
§04:00 – 05:00 362 MW
5. Amount of LTTR remaining after curtailment :
Slovenia to Italy
21/04/2020
§00:00 – 01:00 281 MW
§01:00 – 02:00 281 MW
§02:00 – 03:00 281 MW
§03:00 – 04:00 281 MW
§04:00 – 05:00 288 MW
6 Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *
Voltage stability issue on the Italian Electrical system.
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.