Daily Curtailment Notification for Market Period 03/05/2025 - (AT-IT, GR-IT, IT-GR, IT-FR, FR-IT, SI-IT, IT-SI, CH-IT)
Capacity Curtailment on the AT-IT border for delivery period 03-05-2025
1. TSO(s)*:
TERNA
2. Identification of affected Long Term Transmission Rights:
AT-IT
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 08:00 - 09:00 71 MW
03-05-2025 09:00 - 10:00 71 MW
03-05-2025 10:00 - 11:00 71 MW
03-05-2025 11:00 - 12:00 71 MW
03-05-2025 12:00 - 13:00 71 MW
03-05-2025 13:00 - 14:00 71 MW
03-05-2025 14:00 - 15:00 71 MW
03-05-2025 15:00 - 16:00 71 MW
03-05-2025 16:00 - 17:00 71 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 08:00 - 09:00 55 MW
03-05-2025 09:00 - 10:00 55 MW
03-05-2025 10:00 - 11:00 55 MW
03-05-2025 11:00 - 12:00 55 MW
03-05-2025 12:00 - 13:00 55 MW
03-05-2025 13:00 - 14:00 55 MW
03-05-2025 14:00 - 15:00 55 MW
03-05-2025 15:00 - 16:00 55 MW
03-05-2025 16:00 - 17:00 55 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
Expected violation of operational security limits of physical transmission assets
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC
Capacity Curtailment on the GR-IT border for delivery period 03-05-2025
1. TSO(s)*:
TERNA, ADMIE
2. Identification of affected Long Term Transmission Rights:
GR-IT
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 00:00 - 01:00 50 MW
03-05-2025 01:00 - 02:00 50 MW
03-05-2025 02:00 - 03:00 50 MW
03-05-2025 03:00 - 04:00 50 MW
03-05-2025 04:00 - 05:00 50 MW
03-05-2025 05:00 - 06:00 50 MW
03-05-2025 06:00 - 07:00 50 MW
03-05-2025 07:00 - 08:00 50 MW
03-05-2025 08:00 - 09:00 50 MW
03-05-2025 09:00 - 10:00 50 MW
03-05-2025 10:00 - 11:00 50 MW
03-05-2025 11:00 - 12:00 50 MW
03-05-2025 12:00 - 13:00 50 MW
03-05-2025 13:00 - 14:00 50 MW
03-05-2025 14:00 - 15:00 50 MW
03-05-2025 15:00 - 16:00 50 MW
03-05-2025 16:00 - 17:00 50 MW
03-05-2025 17:00 - 18:00 50 MW
03-05-2025 18:00 - 19:00 50 MW
03-05-2025 19:00 - 20:00 50 MW
03-05-2025 20:00 - 21:00 50 MW
03-05-2025 21:00 - 22:00 50 MW
03-05-2025 22:00 - 23:00 50 MW
03-05-2025 23:00 - 24:00 50 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 00:00 - 01:00 0 MW
03-05-2025 01:00 - 02:00 0 MW
03-05-2025 02:00 - 03:00 0 MW
03-05-2025 03:00 - 04:00 0 MW
03-05-2025 04:00 - 05:00 0 MW
03-05-2025 05:00 - 06:00 0 MW
03-05-2025 06:00 - 07:00 0 MW
03-05-2025 07:00 - 08:00 0 MW
03-05-2025 08:00 - 09:00 0 MW
03-05-2025 09:00 - 10:00 0 MW
03-05-2025 10:00 - 11:00 0 MW
03-05-2025 11:00 - 12:00 0 MW
03-05-2025 12:00 - 13:00 0 MW
03-05-2025 13:00 - 14:00 0 MW
03-05-2025 14:00 - 15:00 0 MW
03-05-2025 15:00 - 16:00 0 MW
03-05-2025 16:00 - 17:00 0 MW
03-05-2025 17:00 - 18:00 0 MW
03-05-2025 18:00 - 19:00 0 MW
03-05-2025 19:00 - 20:00 0 MW
03-05-2025 20:00 - 21:00 0 MW
03-05-2025 21:00 - 22:00 0 MW
03-05-2025 22:00 - 23:00 0 MW
03-05-2025 23:00 - 24:00 0 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
HVDC cable ARACTHOS – GALATINA
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation
Capacity Curtailment on the IT-GR border for delivery period 03-05-2025
1. TSO(s)*:
TERNA, ADMIE
2. Identification of affected Long Term Transmission Rights:
IT-GR
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 00:00 - 01:00 50 MW
03-05-2025 01:00 - 02:00 50 MW
03-05-2025 02:00 - 03:00 50 MW
03-05-2025 03:00 - 04:00 50 MW
03-05-2025 04:00 - 05:00 50 MW
03-05-2025 05:00 - 06:00 50 MW
03-05-2025 06:00 - 07:00 50 MW
03-05-2025 07:00 - 08:00 50 MW
03-05-2025 08:00 - 09:00 50 MW
03-05-2025 09:00 - 10:00 50 MW
03-05-2025 10:00 - 11:00 50 MW
03-05-2025 11:00 - 12:00 50 MW
03-05-2025 12:00 - 13:00 50 MW
03-05-2025 13:00 - 14:00 50 MW
03-05-2025 14:00 - 15:00 50 MW
03-05-2025 15:00 - 16:00 50 MW
03-05-2025 16:00 - 17:00 50 MW
03-05-2025 17:00 - 18:00 50 MW
03-05-2025 18:00 - 19:00 50 MW
03-05-2025 19:00 - 20:00 50 MW
03-05-2025 20:00 - 21:00 50 MW
03-05-2025 21:00 - 22:00 50 MW
03-05-2025 22:00 - 23:00 50 MW
03-05-2025 23:00 - 24:00 50 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 00:00 - 01:00 0 MW
03-05-2025 01:00 - 02:00 0 MW
03-05-2025 02:00 - 03:00 0 MW
03-05-2025 03:00 - 04:00 0 MW
03-05-2025 04:00 - 05:00 0 MW
03-05-2025 05:00 - 06:00 0 MW
03-05-2025 06:00 - 07:00 0 MW
03-05-2025 07:00 - 08:00 0 MW
03-05-2025 08:00 - 09:00 0 MW
03-05-2025 09:00 - 10:00 0 MW
03-05-2025 10:00 - 11:00 0 MW
03-05-2025 11:00 - 12:00 0 MW
03-05-2025 12:00 - 13:00 0 MW
03-05-2025 13:00 - 14:00 0 MW
03-05-2025 14:00 - 15:00 0 MW
03-05-2025 15:00 - 16:00 0 MW
03-05-2025 16:00 - 17:00 0 MW
03-05-2025 17:00 - 18:00 0 MW
03-05-2025 18:00 - 19:00 0 MW
03-05-2025 19:00 - 20:00 0 MW
03-05-2025 20:00 - 21:00 0 MW
03-05-2025 21:00 - 22:00 0 MW
03-05-2025 22:00 - 23:00 0 MW
03-05-2025 23:00 - 24:00 0 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
HVDC cable ARACTHOS – GALATINA
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation
Capacity Curtailment on the IT-FR border for delivery period 03-05-2025
1. TSO(s)*:
TERNA
2. Identification of affected Long Term Transmission Rights:
IT-FR
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 07:00 - 08:00 1869 MW
03-05-2025 08:00 - 09:00 1869 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 07:00 - 08:00 1818 MW
03-05-2025 08:00 - 09:00 1818 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
Expected violation of operational security limits of physical transmission assets
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC
Capacity Curtailment on the FR-IT border for delivery period 03-05-2025
1. TSO(s)*:
TERNA
2. Identification of affected Long Term Transmission Rights:
FR-IT
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 08:00 - 09:00 423 MW
03-05-2025 09:00 - 10:00 423 MW
03-05-2025 10:00 - 11:00 423 MW
03-05-2025 11:00 - 12:00 423 MW
03-05-2025 12:00 - 13:00 423 MW
03-05-2025 13:00 - 14:00 423 MW
03-05-2025 14:00 - 15:00 423 MW
03-05-2025 15:00 - 16:00 423 MW
03-05-2025 16:00 - 17:00 423 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 08:00 - 09:00 224 MW
03-05-2025 09:00 - 10:00 22 MW
03-05-2025 10:00 - 11:00 22 MW
03-05-2025 11:00 - 12:00 22 MW
03-05-2025 12:00 - 13:00 22 MW
03-05-2025 13:00 - 14:00 22 MW
03-05-2025 14:00 - 15:00 22 MW
03-05-2025 15:00 - 16:00 22 MW
03-05-2025 16:00 - 17:00 217 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
Expected violation of operational security limits of physical transmission assets
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC
Capacity Curtailment on the SI-IT border for delivery period 03-05-2025
1. TSO(s)*:
TERNA
2. Identification of affected Long Term Transmission Rights:
SI-IT
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 08:00 - 09:00 38 MW
03-05-2025 09:00 - 10:00 38 MW
03-05-2025 10:00 - 11:00 38 MW
03-05-2025 11:00 - 12:00 38 MW
03-05-2025 12:00 - 13:00 38 MW
03-05-2025 13:00 - 14:00 38 MW
03-05-2025 14:00 - 15:00 38 MW
03-05-2025 15:00 - 16:00 38 MW
03-05-2025 16:00 - 17:00 38 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 08:00 - 09:00 11 MW
03-05-2025 09:00 - 10:00 1 MW
03-05-2025 10:00 - 11:00 1 MW
03-05-2025 11:00 - 12:00 1 MW
03-05-2025 12:00 - 13:00 1 MW
03-05-2025 13:00 - 14:00 1 MW
03-05-2025 14:00 - 15:00 1 MW
03-05-2025 15:00 - 16:00 1 MW
03-05-2025 16:00 - 17:00 28 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
Expected violation of operational security limits of physical transmission assets
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC
Capacity Curtailment on the IT-SI border for delivery period 03-05-2025
1. TSO(s)*:
TERNA
2. Identification of affected Long Term Transmission Rights:
IT-SI
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 15:00 - 16:00 315 MW
03-05-2025 16:00 - 17:00 315 MW
03-05-2025 17:00 - 18:00 315 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 15:00 - 16:00 269 MW
03-05-2025 16:00 - 17:00 269 MW
03-05-2025 17:00 - 18:00 269 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
Expected violation of operational security limits of physical transmission assets
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC
Capacity Curtailment on the CH-IT border for delivery period 03-05-2025
1. TSO(s)*:
SWISSGRID
2. Identification of affected Long Term Transmission Rights:
CH-IT
3. Triggering event:
Curtailment to ensure operation remains within Operational Security Limits
4. Affected volume in MW / hour for each concerned period:
03-05-2025 08:00 - 09:00 285 MW
03-05-2025 09:00 - 10:00 285 MW
03-05-2025 10:00 - 11:00 285 MW
03-05-2025 11:00 - 12:00 285 MW
03-05-2025 12:00 - 13:00 285 MW
03-05-2025 13:00 - 14:00 285 MW
03-05-2025 14:00 - 15:00 285 MW
03-05-2025 15:00 - 16:00 285 MW
03-05-2025 16:00 - 17:00 285 MW
5. Amount of LTTR remaining after curtailment:
03-05-2025 08:00 - 09:00 78 MW
03-05-2025 09:00 - 10:00 0 MW
03-05-2025 10:00 - 11:00 0 MW
03-05-2025 11:00 - 12:00 0 MW
03-05-2025 12:00 - 13:00 0 MW
03-05-2025 13:00 - 14:00 0 MW
03-05-2025 14:00 - 15:00 0 MW
03-05-2025 15:00 - 16:00 0 MW
03-05-2025 16:00 - 17:00 69 MW
6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment*:
7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s)*?
*According to section 57.3 of the EU HAR, this field can be filled in within 24 hours after the initial publication